HPT-T
Multi-segment Temperature Controller
The HPT-T is a panel instrument for multi-segment temperature control using an external sensor or transmitter input. Configurations include analogue, relay, SSR and SCR control outputs, with serial communication options.
- Measurement accuracy
- ±0.2% FS
- Analogue control-output configurations
- 4–20 mA / 0–10 mA / 0–20 mA / 1–5 V / 0–5 V / 0–10 V
- Other control-output configurations
- Relay / SCR / SSR driver / three-phase SCR trigger
Supplied by WKSENSOR. Ask us about pricing, availability and delivery.
Product overview
Panel temperature controller
A wide front panel with four side keys, a fixing bracket and a vented rear housing.
Overall dimensions: 160 × 80 × 110 mm. LED numerical and bar indication for PV and SV.
Multi-segment control and alarm indication
External measurement inputs include thermocouples, three-wire Pt100 and two-wire current transmitters. Alarm functions include upper and lower limits, deviation and control-loop break detection, with hysteresis settings.
Panel and case envelope
Overall width × height × depth: 160 × 80 × 110 mm.
Configuration and selection
Measurement input connections
The illustrated 36-terminal configuration separates measurement input, transmitter feed and control output. Other case formats use different terminal arrangements.
| Three-wire Pt100 | 22: A; 23 and 24: B |
|---|---|
| RTD lead reference | Equal lead resistances; ≤15 Ω per lead |
| Thermocouple | 23: +; 24: − |
| 4–20 mA input | 20: +; 24: − |
| Transmitter feed | 7: DC24V +; 8: − |
| 4–20 mA control output | 25: +; 26: − |
| SSR-driver example | 25: DC12V +; 26: − |
| Illustrated mains | 11: L; 12: N |
Serial communication references
| RS485 | Two-wire; specified distance ≤1000 m |
|---|---|
| RS232 | Three-wire; specified distance ≤15 m |
| Data framing | 1 start bit; 8 data bits; 1 stop bit; no parity |
| Protocol / rate | Modbus RTU; 1200–19200 bps |
Control-output reference
| Output version | Rating |
|---|---|
| Analogue control | 4–20 mA / 0–10 mA / 0–20 mA / 1–5 V / 0–5 V / 0–10 V |
| K1 relay, small contact | 125 V AC / 0.5 A or 24 V DC / 0.5 A; resistive load |
| K1 relay, large contact | 220 V AC / 2 A or 24 V DC / 2 A; resistive load |
| K3 bidirectional SCR trigger | 400 V AC / 5 A |
| K4 SSR driver | 12 V DC / 30 mA |
| K6 SCR | Three-phase SCR trigger version |
Measurement input: thermocouple, three-wire Pt100 or two-wire 4–20 mA transmitter. Power versions: AC/DC 100–240 V or 20–29 V DC.
RS485 or RS232 versions use Modbus RTU. An RS232 microprinter interface is an option.
Technical reference
Specifications and options
| Parameter | Specification or option |
|---|---|
| Model | HPT-T |
| Overall dimensions | 160 × 80 × 110 mm |
| Indication | LED; PV / SV numerical and bar indication |
| Display scaling | −1999–9999 |
| Measurement accuracy | ±0.2% FS |
| Input configurations | Thermocouple / three-wire Pt100 / two-wire 4–20 mA transmitter |
| Analogue control-output configurations | 4–20 mA / 0–10 mA / 0–20 mA / 1–5 V / 0–5 V / 0–10 V |
| Other control-output configurations | Relay / SCR / SSR driver / three-phase SCR trigger |
| Communication configurations | Two-wire RS485 / three-wire RS232 |
| Serial protocol | Modbus RTU |
| Baud-rate configurations | 1200–19200 bps |
| Supply configurations | AC/DC 100–240 V / DC 20–29 V |
| Power consumption | ≤5 W for the 100–240 V supply version; ≤3 W for the 20–29 V DC version |
| Operating ambient | −10–50 °C; non-condensing and no freezing |
| Brand | WKSENSOR |
| Product reference | HH-842380359370 |
Application scenarios
Industrial control applications
Panel indication and control using signals from external process sensors or transmitters.
- Power
- Petrochemicals
- Metallurgy
- Papermaking
- Food
- Light industry
- Pharmaceuticals
- Heat treatment
- Water treatment
- Machinery